Eccentric Holdowns in Light-Framed Shear Wall Systems
This is an increasingly expansive and complex topic whereby one ultimately asks "Do post failures in field-built shear walls occur due to eccentric type holdowns?" Based on years of light-framed shear wall testing, we find no evidence to support this contention. In addition, we know of no documented evidence attributing shear wall failures to post failures caused by eccentric holdowns, in either single or multi-story structures, during past seismic events.
Designing
Shear Wall Posts for Eccentricity
The
internal post stresses calculated in a 'bare post' approach
are very conservative and unwarranted at this time. This type
of simplified static analysis of a single component in a shear
wall system, with numerous elements that interact in very
complex ways, will be highly inaccurate. Testing has verified
that post failures rarely occur even at ultimate wall strength
levels, although calculations by the "bare-post" method often
produce ultimate demand-to-allowable stress level capacity
(D/C) ratios in the range of 5 to 9. Any wood member with
a D/C ratio over 3 would be expected to fail.
ICBO
Position
ICBO
issued a document, dated January 17, 2000, which states, "While
there is agreement that a bare (unsheathed) post loaded by
an eccentric connection can be adequately evaluated using
a simple free body diagram, the same cannot be said for a
member that is braced by sheathing/fasteners applied to one
or both sides of the post."
Conclusion
A
desire for safer structures is the common goal for all involved
in the building industry. However, premature design recommendations
for eccentricity should not be included in this process. The
Building Seismic Safety Council (BSSC) Technical Subcommittee
7 has been tasked to study this issue. The BSSC is contracted
by FEMA to write the NEHRP provisions, which serve as the
basis for seismic provisions in the IBC, IRC, ASCE 7, and
NFPA 5000 codes. The task of this committee will be to determine
the appropriate design procedures for shear wall boundary
members due to several different limit states. As a manufacturer
of both eccentric and concentric type holdowns, we support
the efforts of this committee to ultimately determine if the
eccentric holdown issue is a concern and, if so, what rational
based recommendations should be implemented.